V90: Gsdml-v2.32-siemens-sinamics
Telegram 3 = Speed control with basic I/O (16 bytes each direction):
| PLC → Drive (Output) | Drive → PLC (Input) | |-------------------------|-------------------------| | Control word (STW1) | Status word (ZSW1) | | Speed setpoint (NSOLL_B) | Actual speed (NIST_B) | | – | Active fault code | Gsdml-v2.32-siemens-sinamics V90
Telegram 102 (positioning):
To use the SINAMICS V90 in "External Position Mode" (EPOS), GSDML v2.32 is mandatory. EPOS allows the PLC to send absolute position targets (e.g., move to 500.0 mm). Telegram 3 = Speed control with basic I/O
| Issue | Solution | |-------|----------| | V90 not found after GSDML install | Check firmware compatibility; V90 requires FW ≥ V1.0 for PROFINET. | | IO device fails to start | Verify device name matches exactly (case-sensitive). | | Telegram mismatch | Recompile hardware configuration; ensure telegram selected matches V90 parameter p0922. | | Cyclic communication timeout | Reduce send clock or check network load (e.g., 1 ms cycle may be too fast). | To use the SINAMICS V90 in "External Position
The GSDML file defines the binary structure of data sent cyclically. The V90 GSDML typically includes the following standard telegram definitions:
The jump to v2.32 offers two tangible improvements for the V90: